ABOUT HQ-M 60-120KVA ONLINE RACKMOUNT MODULAR UPS
Modular UPS can be widely used in postal communications, financial securities, government agencies, energy and chemical industry, transportation, industrial and commercial taxation, medical and health, national defense and military and other electrical equipment that require reliable power supply.
◆FEATURE
Modular design
The cabinet can be configured with up to 7 main power modules; the modular design of the system can be designed according to future system needs, and the modules can be configured according to the existing load, significantly reducing one-time investment costs.
High Reliability
*Distributed control system for power module
*Isolated air duct for key components
*BMS monitors battery information in real time
*Online UPS: online double conversion
Green Performance
*Efficiency up to 96%
*Output PF = 1
*Maintenance bypass mode
*THDi < 3% and input PF > 0.99
◆OTHER
Offering scalability for easy expansion or reduction of capacity
Rack-mountable for optimized space efficiency
Capacity: 40kVA/50kVA/80kVA/100kVA/120kVA/150kVA
Topology: online double conversion
Specification
Model | HQ-M60 | HQ-M75 | HQ-M80 | HQ-M100 | HQ-M120 |
Capacity | 60kVA | 75kVA | 80kVA | 100kVA | 120kVA |
Cabinet Type | 4 Modules | 7 Modules | |||
Power Module Capacity | 10/15/20kVA | 25kVA | 10/15/20kVA | 25kVA | 10/15/20kVA |
Input | |||||
Rated Voltage | 3 Phase+N+PE 380/400/415VAC(Line voltage) | ||||
Rated Frequency | 50/60Hz | ||||
Voltage Range (Full Load) | 304~478VAC | ||||
Frequency Range | 40 ~ 70Hz | ||||
Power Factor | >0.99 | ||||
THDi | <3%(100% linear load);< 5%(100% non-linear load) | ||||
Bypass | |||||
Rated Voltage | 380/400/415VAC(Line voltage) | ||||
Voltage Range | Default: -20% ~ +15%;configurable, upper limit: +10%, +15%, +20%, +25%;lower limit: -10%, -15%, -20%, -30%, -40% | ||||
Battery | |||||
Voltage | ±192VDC(±180 ~ ±264VDC, 30 - 44 units configurable, default: 32 units) | ||||
Output | |||||
Rated Voltage | 380V/400V/415V(Line voltage) | ||||
Rated Frequency | 50/60Hz | ||||
Power Factor | 1 | ||||
Voltage Accuracy | ≤±1.0% @ balanced load ;≤±5.0% @ unbalanced load | ||||
Frequency Accuracy | 50/60Hz ± 0.1% | ||||
Frequency Tracking Range | ±0.5Hz ~ ±5Hz, configurable, default: ±3Hz | ||||
THDu | ≤2%(100% linear load), ≤4%(nonlinear load) | ||||
Three-Phase Accuracy | 120° ± 1° | ||||
Crest Factor | 3:01 | ||||
Overload | ≤105%, long run; 105% ~ 110%, 60min; 110 ~ 125%, 10min;125 ~150%, 1min; >150%, switch to the bypass immediately | ||||
System | |||||
Efficiency | 96% | ||||
Display | 7” Touch screen + LED | ||||
Standard | IEC62040-1-1; IEC62040-2; IEC62040-3 | ||||
Optional | Lightning protection module, dustproof net, load break switch cable, seismic kit | ||||
Protection Class | IP20 | ||||
Communication | RS232/ RS485, optional: SNMP/dry contact | ||||
Operating Temperature | 0 ~ 40°C | ||||
Humidity | 0 ~ 95%(Non-condensing) | ||||
Altitude | <1000M no derate, >1000m derate 1% per 100m | ||||
Noise | <65dB @ 1m | ||||
Size | |||||
System W x D x H(mm) | 600 x 850 x 1200 | ||||
Module W x D x H(mm) | 440 x 690 x 86(2U) | ||||
Weight | |||||
System(kg) | 145 | 210 | |||
Module(kg) | 20(10kVA), 22(15kVA), 24(20kVA), 25(25kVA) |