ABOUT DTH33 3 PHASE 500KVA ONLINE UPS
Applications: Telecommunications, financial services, security systems, data centers, medical apparatus, and industrial control devices.
◆FEATURE
Advanced Technology
*Input: 304~478VAC
*50/60Hz Auto-sensing
*Parallel redundancy (N+X) UPS system
*Self-test function
*Generator UPS compatibility
Outstanding Flexibility
*Battery numbers configurable
*10" LCD touch screen
*Mains power start
*UPS with cold start
*500kVA UPS, capacity available in 200kVA/300kVA/400kVA/500kVA/600kVA
*Economy mode included
*Power factor correction technology
*Communication: RS232, RS485, dry contact or SNMP
◆OTHER
Lithium-ion battery technology
3 Phase Input, 3 Phase Output
Capacity: 200kVA/300kVA/400kVA/500kVA/600kVA
More cost effective and offers faster response times to power fluctuations
SPECIFICATION
Model | DTH33-200KL | DTH33-300KL | DTH33-400KL | DTH33-500KL | DTH33-600KL |
Capacity | 200kVA | 300kVA | 400kVA | 500kVA | 600kVA |
Input | |||||
Rated Voltage | (3 Phase+N+PE) 380/400/415VAC | ||||
Voltage Range | 304~478VAC (line voltage) full load; 208~304VAC (line voltage) | ||||
Frequency Range | 50/60Hz (range: 40Hz ~ 70Hz) | ||||
Power Factor | ≥0.99 | ||||
THDi | <3% (100% linear load); <5% (100% nonlinear load) | ||||
Output | |||||
Voltage | 380/400/415VAC (3 Phase+N) | ||||
Voltage Accuracy | ±1% | ||||
Frequency Range | Synchronization Range: ±0.5Hz, ±1Hz, ±2Hz, ±3Hz(configurable) Battery Mode: 50Hz ± 0.1Hz or 60Hz ± 0.1Hz | ||||
Overload | 105%~110%, 60min; 110%~125%, 10min; 125%~150%, 1min; >150%, 0.2sec | ||||
Power Factor | 1 | ||||
THDu | ≤2% @ (100% linear load);≤4% @ (100% nonlinear load) | ||||
Crest Factor | 3:1(Maximum) | ||||
Switching Time | 0ms | ||||
Efficiency | |||||
Inverter Mode | 96% |