HQ-M Online Three Phase Modular UPS

  • HQ-M Online Three Phase Modular UPS
  • video
  • EVADA
  • CHINA
Applications: Finance, telecom, education, transportation power, taxation, medical, enterprise, petrochemical, etc.

ABOUT HQ-M ONLINE THREE PHASE MODULAR UPS


EVADA HQ-M Three Phase Modular UPS, with a 25kVA UPS capacity (available in the range of 10kVA to 300kVA) is a versatile solution. This modular online UPS, featuring a double conversion design, serves as a perfect back UPS for various applications. The EVADA HQ-M Modular UPS combines double conversion online UPS capability and 3 phase modular UPS scalability, offers easy expansion and customization.



◆FEATURE


3812-202401231505272209.jpg

Intelligent Flexibility

*Hot-swappable bypass/power module

*30-44 units battery configurable

*Allowing common battery group for parallel

*7" Color touchscreen

*Cold start function

3812-202401231505278319.jpg

High Reliability

*Distributed control system for power module

*Isolated air duct for key components

*BMS monitors battery information in real time

*Power module N+X redundancy design

3812-202401231505272836.jpg

Green Performance

*ECO mode for energy saving

*Efficiency up to 96%Output PF = 1

*Maintenance bypass mode

*THDi < 3% and input PF > 0.99


◆OTHER


Modular Online UPS

N+X redundancy design

Three Phase Modular UPS

Three Phase Input, Three Phase Output

25kVA UPS

Capacity: 10kVA-300kVA

Double Conversion Online UPS

Online double conversion topology, high input PF>0.99

Back UPS

Battery management system continuously tracks and reports battery status and performance


SPECIFICATION



Model HQ-M60HQ-M75HQ-M80 HQ-M100 HQ-M120HQ-M140HQ-M150
HQ-M175HQ-M200HQ-M300
Capacity 60kVA 75kVA 80kVA 100kVA 120kVA140kVA150kVA175kVA200kVA300kVA
Cabinet TypeModulesModules12 Modules
Power Module Capacity10/15/20kVA25kVA10/15/20kVA25kVA10/15/20kVA25kVA10/15/20kVA25kVA
Input
Rated Voltage3 Phase+N+PE 380/400/415VAC (Line voltage)
Rated Frequency\50/60Hz
Voltage Range 304~478VAC
Frequency Range (Full Load) 40 ~ 70Hz
Power Factor >0.99
THDi <3% (100% linear load); <5% (100% nonlinear load)
Output
Rated Voltage 380V/400V/415V(Line voltage)
Rated Frequency50/60Hz
Voltage Accuracy ≤±1.0% @ balanced load;≤±5.0% @ unbalanced load
Frequency Accuracy50/60Hz ± 0.1%
Frequency Tracking Range±0.5Hz ~ ±5Hz, configurable, default: ±3Hz
Overload ≤105%,long run; 105% ~ 110%,60min; 110 ~ 125%,10min;125~150%,1min; >150%,switch to the bypass immediately
Power Factor 1
THDu ≤2% @ (100% linear load);≤4% @ (100% nonlinear load)
Crest Factor3:1
Three-Phase Accuracy 120° ± 1°
Bypass
Rated Voltage 380V/400V/415V(Line voltage)
Voltage RangeDefault: -20% ~ +15%;configurable, upper limit: +10%, +15%, +20%, +25%;lower limit: -10%, -15%, -20%, -30%, -40%



Get the latest price? We will reply as soon as possible (within 12 hours)