ABOUT HQ-M 3 PHASE 60KVA MODULAR UPS
The EVADA HQ-M 3 Phase 60kVA Modular UPS – a scalable UPS device offering flexibility with 50kVA UPS modules (available in the range of 40kVA to 800kVA). This UPS power supply is engineered for reliability and efficiency, providing adaptable power solutions for a wide range of industry applications.
◆FEATURE
Intelligent Flexibility
*30-44 units battery configurable
*Hot-swappable bypass/power module
*Allowing common battery group for parallel
*Fan speed automatically adjusts according to the load
*Multiple communication methods
*Cold start function
High Reliability
*Distributed control system for power module
*Isolated air duct for key components
*BMS monitors battery information in real time
*Power module N+X redundancy design50kVA
*Module with display&indicators
Green Performance
*Efficiency up to 96%
*Output PF = 1
*Maintenance bypass mode
*THDi < 3% and input PF > 0.99
*ECO mode efficiency up to 99%
◆OTHER
Hot swappable module for easy operation
3 Phase Input, 3 Phase Output
Capacity: 40kVA-800kVA
Efficiency: up to 96%
SPECIFICATION
Model | HQ-M200 | HQ-M300 | HQ-M400 | HQ-M500 | HQ-M600 | HQ-M800 |
Capacity | 200kVA | 300kVA | 400kVA | 540kVA | 600kVA | 800kVA |
Cabinet Type | 5(4+1) Modules | 7(6+1) Modules | 12(8+4) Modules | 12(10+2) Modules | 12 Modules | 14 Modules |
Power Module Capacity | 40kVA/50kVA | 50kVA | 50kVA/60kVA | 60kVA | ||
Input | ||||||
Rated Voltage | 3 Phase+N+PE 380/400/415VAC (Line voltage) | |||||
Rated Frequency | 50/60Hz | |||||
Voltage Range | 304~478VAC | |||||
Frequency Range | 40 ~ 70Hz | |||||
Power Factor | ≥0.99 | |||||
THDi | <3% (100% linear load); <5% (100% nonlinear load) | |||||
Output | ||||||
Rated Voltage | 380/400/415VAC (Line Voltage) | |||||
Voltage Accuracy | ≤±1.0% @ balanced load;≤±5.0% @ unbalanced load | |||||
Frequency Tracking Range | ±0.5Hz ~ ±5Hz, configurable, default: ±3Hz | |||||
Overload | ≤105%,long run; 105% ~ 110%,60min; 110 ~ 125%,10min;125~150%,1min; >150%,switch to the bypass immediately | |||||
Power Factor | 1 | |||||
THDu | ≤2% @ (100% linear load);≤4% @ (100% nonlinear load) | |||||
Crest Factor | 3:1 |