eLite Pro Solar Energy Hybrid Inverter
eLite Pro Seires works with solar panels and batteries to form an energy storage system. Featuring backup mode to ensure the stable power supply when utility failed
eLite Pro Seires works with solar panels and batteries to form an energy storage system. Featuring backup mode to ensure the stable power supply when utility failed
The 3-5kW single-phase off grid inverter is an all-in-one system for supplying solar power at home. It can be flexibly configured to single-phase or three-phase
Application: Computer, data center, telecom, finance, security, transportation, medical, petrochemical, etc.
ABOUT DTH33 3 PHASE ONLINE DOUBLE CONVERSION UPS
The EVADA DTH33 3 Phase Online Double Conversion UPS, a robust solution ensuring a reliable backup power supply. Its online double conversion ups architecture guarantees clean power delivery, shielding critical systems from voltage fluctuations. Enhanced by lithium ion UPS technology, it’s a 100kVA UPS (also available in 30kVA/40kVA/50kVA/60kVA/80kVA) offers efficient energy storage, minimizing maintenance costs and providing a range of powerful options.
◆FEATURE
Advanced Technology
*Input range: 304~478VAC
*Frequency range: 50/60Hz Auto-sensing
*N+X parallel redundancy
*Automated self-diagnostic testing
*Generator compatibility
*Online double conversion UPS
*Energy-saving ECO mode
*PFC technology (input PF ≥ 0.99)
Outstanding Flexibility
*Configurable battery quantity: options range from 30 to 44 units
*Versatile LCD&LED display
*Main power initiation
*Cold start capability
*Lithium ion UPS function
*Wide capacity range: 100kVA UPS (also available in 30kVA/40kVA/50kVA/60kVA/80kVA)
◆OTHER
Applications across various sectors, including telecom, data centre, medical facility, etc.
Double conversion process provides isolation from power fluctuations
Capacity: 30kVA/40kVA/50kVA/60kVA/80kVA/100kVA
Lithium-ion battery, allowing for easier expansion
SPECIFICATION
Model | DTH33-30KL | DTH33-40KL | DTH33-50KL | DTH33-60KL | DTH33-80KL | DTH33-100KL |
Capacity | 30kVA | 40kVA | 50kVA | 60kVA | 80kVA | 100kVA |
Input | ||||||
Rated Voltage | (3 Phase+N+PE) 380/400/415VAC | |||||
Voltage Range | 304~478VAC (line voltage) full load; 208~304VAC (line voltage) | |||||
Frequency Range | 50/60Hz (range: 40Hz ~ 70Hz) | |||||
Power Factor | ≥0.99 | |||||
THDi | <3% (100% linear load); <5% (100% nonlinear load) | |||||
Output | ||||||
Voltage | 380/400/415VAC (3 Phase+N) | |||||
Voltage Accuracy | ±1% | |||||
Frequency Range | Synchronization Range: ±0.5Hz, ±1Hz, ±2Hz, ±3Hz(configurable) Battery Mode: 50Hz ± 0.1Hz or 60Hz ± 0.1Hz | |||||
Overload | 105%~110%, 60min; 110%~125%, 10min; 125%~150%, 1min; >150%, 0.2sec | |||||
Power Factor | 1 | |||||
THDu | ≤2% @ (100% linear load);≤4% @ (100% nonlinear load) | |||||
Crest Factor | 3:1(Maximum) | |||||
Switching Time | 0ms | |||||
Efficiency | ||||||
Inverter Mode | 95% |