eLite Pro Solar Energy Hybrid Inverter
eLite Pro Seires works with solar panels and batteries to form an energy storage system. Featuring backup mode to ensure the stable power supply when utility failed
eLite Pro Seires works with solar panels and batteries to form an energy storage system. Featuring backup mode to ensure the stable power supply when utility failed
The 3-5kW single-phase off grid inverter is an all-in-one system for supplying solar power at home. It can be flexibly configured to single-phase or three-phase
Application: Computer, data center, telecom, finance, security, transportation, medical, petrochemical, etc.
ABOUT DTH11-R SINGLE PHASE ONLINE RACK UPS
The UPS 2kVA (also available in 1kVA, 3kVA, 6kVA, 10kVA) – a 1 phase UPS ideal for server rack UPS applications. EVADA DTH11-R Rack Mount UPS employs double conversion online technology, ensuring a reliable power source in applications, offering both space optimization and efficient double conversion online capabilities.
◆FEATURE
Advanced Technology
*110~300VAC input range
*50/60Hz Auto-sensing
*Generator compatible
*1 phase UPS, 1 phase input, 1 phase output
*Double conversion online design
Outstanding Flexibility
*6/10kVA: 16-20 battery units (configurable)
*Support RS232, USB, optional: RS485, dry contact, SNMP
*Compact, rack mount UPS
*Versatile and adaptable, suited for use as a server rack UPS
Green Performance
*ECO mode included
*PFC technology
*Input PF ≥ 0.99
*Output power = 1
*Automated fan speed configuration
◆OTHER
Rack mount design, enhances the space efficiency
Single Phase Input, Single Phase Output
Capacity: 1kVA/2kVA/3kVA/6kVA/10kVA
Online double conversion technology
Ideal for deployment in LAN servers and various other server applications
SPECIFICATION
Model | DTH11-1KR/KRL | DTH11-2KR/KRL | DTH11-3KR/KRL | DTH11-6KRL | DTH11-10KRL |
Capacity | 1kVA | 2kVA | 3kVA | 6kVA | 10kVA |
Input | |||||
Voltage Range | 1 Phase (L+N+PE) 110~300VAC | ||||
Frequency Range | 40 ~ 70Hz | ||||
Power Factor | ≥0.99 | ||||
THDi | <3% (100% linear load); <5% (100% nonlinear load) | ||||
Output | |||||
Voltage | 208/220/230/240VAC | ||||
Voltage Accuracy | ±1% | ||||
Frequency Range | 50Hz ± 0.1Hz or 60Hz ± 0.1Hz | ||||
Overload | 102%~110%, 30min; 111%~130%, 10min; 131%~150%, 30sec; >150%, 0.2sec | ||||
Power Factor | 1 | ||||
THDu | ≤2% @ (100% linear load);≤5% @ (100% nonlinear load) | ||||
Switching Time | 0ms | ||||
Efficiency | |||||
Inverter Mode | 94.5% | 95.5% |